Pipe Sizing Calculations

 Pipe size calculation involves considering factors such as flow rate, velocity, pressure drop, and pipe material to determine the appropriate diameter for a piping system. Here's a general approach to pipe size calculation:

  1. Determine the Flow Rate: Identify the desired flow rate for your system, usually specified by the application requirements or pump capacity. The flow rate is typically measured in gallons per minute (GPM) or cubic meters per hour (m³/hr.).

  2. Calculate the Flow Velocity: Decide on the desired flow velocity based on industry standards and the specific application. Recommended flow velocities generally range from 2 to 10 feet per second (fps) or 0.6 to 3 meters per second (m/s). Higher velocities may result in increased friction losses, while lower velocities may cause sediment buildup or inefficient flow.

Flow Velocity = Flow Rate / Cross-Sectional Area

  1. Determine the Pipe Material: Identify the type of pipe material to be used in the system, such as PVC, copper, steel, or others. Each material has different properties, including allowable pressure ratings, corrosion resistance, and friction factors, which can impact the pipe sizing calculations.

  2. Calculate the Required Cross-Sectional Area: To calculate the required cross-sectional area of the pipe, divide the flow rate by the desired flow velocity:

Cross-Sectional Area = Flow Rate / Flow Velocity

  1. Convert the Cross-Sectional Area to Pipe Diameter: Based on the calculated cross-sectional area, use the formula for the area of a circle (A = πr²) to find the required pipe diameter:

Pipe Diameter = 2 * √(Cross-Sectional Area / π)

Alternatively, you can use pipe sizing charts or online pipe sizing calculators specific to your pipe material and industry standards. These tools provide pipe sizes based on various flow rates, velocities, and pressure drop considerations.

  1. Consider Pressure Drop: Evaluate the pressure drop across the system to ensure it remains within acceptable limits. Pressure drop depends on factors such as pipe length, fittings, bends, and frictional losses. Consider using pressure drop calculation methods like the Darcy-Weisbach equation or the Hazen-Williams formula to assess pressure losses and verify the selected pipe size.

It's important to note that pipe sizing is a complex process that requires careful consideration of various factors and often involves iterative calculations to optimize system performance. Consulting with a professional engineer or utilizing specialized software can provide more accurate and tailored results for your specific piping system.

There are various formulas and equations used to calculate pipe size depending on the specific requirements and variables involved in the piping system. Here are some commonly used formulas for pipe sizing:

  1. Reynolds Number (Re): Re = (ρ * V * D) / μ

Where:

  • Re is the Reynolds number
  • ρ is the density of the fluid
  • V is the velocity of the fluid
  • D is the diameter of the pipe
  • μ is the dynamic viscosity of the fluid

The Reynolds number is used to determine the flow regime (laminar, transitional, or turbulent) and helps assess the impact of viscosity on flow behavior.

  1. Darcy-Weisbach Equation for Pressure Drop: ΔP = (f * (L / D) * (ρ * V²) / 2)

Where:

  • ΔP is the pressure drop
  • f is the Darcy friction factor
  • L is the length of the pipe
  • D is the diameter of the pipe
  • ρ is the density of the fluid
  • V is the velocity of the fluid

The Darcy-Weisbach equation calculates the pressure drop due to friction in a pipe and is often used to determine the appropriate pipe diameter based on allowable pressure drop.

  1. Hazen-Williams Equation: Q = 0.849 * C * (D^2.63) * (h^0.54)

Where:

  • Q is the flow rate
  • C is the Hazen-Williams coefficient (dependent on pipe material)
  • D is the diameter of the pipe
  • h is the head loss

The Hazen-Williams equation is commonly used for water flow calculations and is useful for estimating flow rates and determining pipe sizes in water distribution systems.

These formulas provide a starting point for pipe sizing calculations, but it's important to note that there are additional factors and considerations (e.g., specific application requirements, standards, codes, fittings, friction factors) that may require further analysis and adjustments in the sizing process.

Example 1

If you want to use an 80 NB (Nominal Bore) pipe for the pump, we can calculate the flow rate that the 80 NB pipe can handle based on its cross-sectional area.

Let's assume that for an 80 NB pipe, the outer diameter (OD) is approximately 88.9 mm or 0.0889 meters.

  1. Calculate the Cross-Sectional Area of the 80 NB Pipe: The cross-sectional area (A) of a circular pipe can be calculated using the formula:

A = π * (Diameter/2)^2

Substituting the diameter of the 80 NB pipe into the formula:

A = π * (0.0889/2)^2 A ≈ 0.006154 square meters

  1. Determine the Flow Rate: Using the equation Q = A * V, we can calculate the flow rate that the 80 NB pipe can handle based on a desired velocity (V). Let's assume a desired velocity of 2 meters per second (m/s).

Q = A * V Q = 0.006154 square meters * 2 m/s Q ≈ 0.012308 cubic meters per second (m³/s)

  1. Convert the Flow Rate to the Desired Unit: If you prefer the flow rate to be expressed in a different unit, such as liters per second (L/s) or gallons per minute (GPM), you can convert it accordingly.

For example, to convert the flow rate from cubic meters per second to liters per second:

Q = 0.012308 m³/s * 1000 Q ≈ 12.308 L/s

  1. Determine the Flow Rate for an 80 NB Pipe: Therefore, with an 80 NB pipe, the flow rate that can be handled at a desired velocity of 2 m/s is approximately 12.308 liters per second (L/s).

Please note that this calculation assumes ideal flow conditions and does not consider factors such as pressure drop, friction losses, or specific design requirements.

Example 2

To determine the pipe diameter using the equation Q = A * V, where Q is the flow rate, A is the cross-sectional area, and V is the velocity, we can rearrange the equation to solve for the diameter (D).

Here's how we can proceed:

  1. Calculate the Cross-Sectional Area: From the given flow rate Q ≈ 0.012308 cubic meters per second (m³/s) and velocity V = 2 m/s, we can calculate the cross-sectional area (A):

A = Q / V A = 0.012308 m³/s / 2 m/s A = 0.006154 square meters

  1. Determine the Pipe Diameter: Using the formula for the area of a circle (A = π * (Diameter^2) / 4), we can rearrange it to solve for the diameter (D):

Diameter = √((4 * A) / π)

Substituting the calculated cross-sectional area (A) into the equation:

Diameter = √((4 * 0.006154) / π) Diameter ≈ √(0.024616 / π) meters

Approximating the value of π as 3.14:

Diameter ≈ √(0.007828) meters Diameter ≈ 0.088 meters

To convert the diameter to millimeters, multiply by 1000:

Diameter ≈ 0.088 meters * 1000 = 88 mm

Therefore, based on a flow rate of Q ≈ 0.012308 cubic meters per second (m³/s) and a velocity of V = 2 m/s, the pipe diameter required would be approximately 88 mm.

Please note that this calculation assumes ideal flow conditions and does not consider factors such as pressure drop, friction losses, or specific design requirements.